EasyManuals Logo
Home>Trane>Chiller>CVHE

Trane CVHE Troubleshooting

Trane CVHE
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
CVHE-SB-32A 116
Example of Calculating Return Reset:
If:
Reset Ratio = 50%
Start Reset = 25
TWE = 65
TWL = 45
Maximum Reset = 8
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio* (Start Reset - (TWE-TWL))
Degrees of Reset =.5*(25-(65-45))
Degrees of Reset = 2.5
If:
Reset Ratio = 70%
Start Reset = 20
TWE = 60
TWL = 53
Maximum Reset = 14
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio* (Start Reset - (TWE-TWL))
Degrees of Reset =.7*(20-(60-53))

Table of Contents

Other manuals for Trane CVHE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CVHE and is the answer not in the manual?

Trane CVHE Specifications

General IconGeneral
BrandTrane
ModelCVHE
CategoryChiller
LanguageEnglish

Related product manuals