CVHE-SB-32A 47
Module Dip Switch Settings
UCP2 Board Dip Switch Settings
Several of the UCP2 modules have dip switch settings on them, used to set up the board for 2-10
VDC or 4-20 mA signal inputs and/or outputs of the boards. The following are the various switch
settings.
Chiller Module
Options Module
Switch 0-10V 4-20mA
External Base Loading SW2-1 OFF ON (SW2-2 and SW2-3 are not used)
Switch 0-10V 4-20mA
External Current Limit SW2-1 OFF ON (SW2-2 and SW2-3 are not used)
External Chilled Water SW3-1 OFF ON (SW3-2 and SW3-3 are not used)
Tracer COM 3
Switch -1 -2 -3
SW1 OFF OFF OFF
Tracer COM 4
Switch -1 -2 -3
SW1 OFF ON OFF
IPC Buffer
Switch -1 -2 -3
SW1 OFF OFF ON