TAM810
MODEL NO.
BAYEVAC05BK1A
BAYEVAC05LG1A
BAYEVAC08BK1A
BAYEVAC08LG1A
BAYEVAC10BK1A
BAYEVAC10LG1A
BAYEVAC10LG3AA BAYEVBC15BK1A
BAYEVCB15LG3A
BAYEVBC20BK1A
*AM8A0C42V31SAA 978/1093 978/1380 1035/1380 920/1093 1035/1438 1150/1495 1380/1610
MINIMUM HEATER AIRFLOW CFM - HEATER MATRI
WITHOUT HEAT PUMP / WITH HP
SEE AIR HANDLER NAMEPLATE
AM8A0C42 Minimum Heating Airflow Settings
NOTE: Minimum auxiliary heating airflow is automatically configured by the air
handler model and the auxiliary heater model number. This is not field adjustable.
*AM8A0C42 AIRFLOW PERFORMANCE
CONSTANT CFM MODE / CONSTANT TORQUE MODE
OUTDOOR
MULTIPLIER
(TONS)
COOLING
AIRFLOW
SETTING
Airflow
Power
EXTERNAL STATIC PRESSURE (Constant CFM / Constant Torque)
HEATING
AIRFLOW
SETTING
Airflow
Power
EXTERNAL STATIC PRESSURE
0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9
2.5 tons
290
CFM/ton
CFM
Watts
747 / 905
48 / 77
743 / 764
87 / 94
742 / 591
127 / 102
741 / 342
168 / 106
739 / NA
207 / NA
290
CFM/ton
CFM
Watts
744
51
741
90
740
130
738
170
734
209
370
CFM/ton
CFM
Watts
937 / 1072
80 / 118
942 / 956
129 / 139
946 / 823
179 / 151
947 / 655
227 / 155
944 / 458
273 / 155
350
CFM/ton
CFM
Watts
889
76
892
123
894
169
894
215
890
259
400
CFM/ton
CFM
Watts
1006 / 1136
95 / 138
1014 / 1027
148 / 159
1020 / 903
201 / 173
1022 / 760
253 / 178
1019 / 586
302 / 177
400
CFM/ton
CFM
Watts
1006
103
1016
156
1018
209
1019
160
1016
308
450
CFM/ton
CFM
Watts
1122 / 1247
125 / 176
1135 / 1146
185 / 200
1143 / 1035
245 / 216
1146 / 911
303 / 224
1142 / 768
357 / 223
450
CFM/ton
CFM
Watts
1124
136
1135
196
1142
256
1144
313
1140
366
3 tons
290
CFM/ton
CFM
Watts
885 / 1026
70 / 106
889 / 904
116 / 125
891 / 763
163 / 136
892 / 590
209 / 139
889 / 341
254 / 143
290
CFM/ton
CFM
Watts
884
75
887
121
889
168
889
214
885
257
370
CFM/ton
CFM
Watts
1108 / 1233
121 / 171
1120 / 1132
181 / 195
1128 / 1019
240 / 210
1131 / 893
297 / 218
1128 / 747
350 / 217
350
CFM/ton
CFM
Watts
1053
115
1062
171
1067
227
1069
280
1066
330
400
CFM/ton
CFM
Watts
1194 / 1316
147 / 204
1208 / 1220
212 / 229
1218 / 1115
276 / 246
1221 / 999
337 / 255
1215 / 868
393 / 256
400
CFM/ton
CFM
Watts
1196
160
1209
225
1218
289
1219
349
1212
403
450
CFM/ton
CFM
Watts
1343 / 1463
200 / 272
1361 / 1374
275 / 300
1371 / 1279
348 / 320
1368 / 1175
413 / 331
1352 / 1061
469 / 334
450
CFM/ton
CFM
Watts
1347
220
1363
295
1371
367
1366
430
1342
480
3.5 tons †
290
CFM/ton
CFM
Watts
1020 / 1149
99 / 142
1028 / 1041
152 / 164
1034 / 919
206 / 178
1037 / 779
259 / 183
1034 / 609
308 / 182
290
CFM/ton
CFM
Watts
1020
107
1028
160
1033
214
1173
327
1031
315
370 †
CFM/ton
CFM
Watts
1287 / 1408
179 / 245
1304 / 1317
250 / 272
1314 / 1218
320 / 291
1315 / 1110
384 / 301
1304 / 981
441 / 303
350
CFM/ton
CFM
Watts
1220
169
1234
236
1243
301
1244
362
1236
417
400
CFM/ton
CFM
Watts
1395 / 1514
221 / 299
1413 / 1427
300 / 328
1421 / 1334
374 / 348
1415 / 1233
440 / 361
1369 / 1124
480 / 364
400 †
CFM/ton
CFM
Watts
1440
244
1416
322
1421
395
1411
458
1355
475
450
CFM/ton
CFM
Watts
1584 / 1687
313 / 405
1593 / 1605
399 / 435
1576 / 1518
467 / 458
1474 / 1425
477 / 472
1350 / 1326
468 / 477
450
CFM/ton
CFM
Watts
1589
347
1592
428
1545
474
1434
473
1315
463
4 tons
290
CFM/ton
CFM
Watts
1156 / 1302
135 / 197
1169 / 1205
197 / 222
1178 / 1098
259 / 239
1181 / 981
319 / 248
1174 / 848
383 / 249
290
CFM/ton
CFM
Watts
1157
147
1169
209
1177
271
1179
330
1174
383
370
CFM/ton
CFM
Watts
1487 / 1618
288 / 359
1500 / 1534
369 / 389
1496 / 1445
441 / 411
1445 / 1350
481 / 425
1319 / 1248
470 / 429
350
CFM/ton
CFM
Watts
1400
244
1416
322
1421
395
1411
458
1335
475
400
CFM/ton
CFM
Watts
1616 / 1728
363 / 433
1614 / 1646
443 / 464
1543 / 1543
475 / 475
1423 / 1423
472 / 472
1301 / 1301
463 / 463
400
CFM/ton
CFM
Watts
1615
363
1615
444
1545
474
1431
471
1313
462
450
CFM/ton
CFM
Watts
1711 / 1711
432 / 432
1621 / 1621
456 / 456
1514 / 1514
465 / 465
1393 / 1393
460 / 460
1273 / 1273
453 / 453
450
CFM/ton
CFM
Watts
1716
430
1629
453
1528
462
1411
458
1297
452
NOTES:
1. * Models start with "A" or "T"
2. † Factory Setting
3. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
4. Torque mode will reduce airflow when static is above approximately
0.35” water column.
5. All heating modes default to Constant CFM.
6. Cooling airflow values are with wet coil, no filter