EasyManuals Logo

Trane Hyperion AAM8A0C48V41CA User Manual

Trane Hyperion AAM8A0C48V41CA
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
TAM811
*AM8A0C48 AIRFLOW PERFORMANCE
CONSTANT CFM MODE / CONSTANT TORQUE MODE
OUTDOOR
MULTIPLIER
(TONS)
COOLING
AIRFLOW
SETTING
Airflow
Power
EXTERNAL STATIC PRESSURE (Constant CFM / Constant Torque)
HEATING
AIRFLOW
SETTING
Airflow
Power
EXTERNAL STATIC PRESSURE
0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9
3 tons
290
CFM/ton
CFM
Watts
894 / 1018
69 / 91
900 / 897
114 / 114
896 / 767
157 / 130
886 / 622
195 / 137
871 / 445
229 /
290
CFM/ton
CFM
Watts
893
72
900
118
893
159
883
197
864
230
350
CFM/ton
CFM
Watts
1067 / 1180
106 / 132
1073 / 1078
158 / 160
1072 / 972
208 / 180
1065 / 859
252 / 192
1053 / 738
292 / 194
350
CFM/ton
CFM
Watts
1068
112
1073
164
1070
213
1062
257
1049
295
400
CFM/ton
CFM
Watts
1205 /1314
145 / 176
1212 / 1222
203 / 206
1213 / 1128
259 / 229
1208 / 1029
309 / 244
1199 / 926
354 / 249
400
CFM/ton
CFM
Watts
1207
154
1212
212
1212
266
1206
315
1196
359
450
CFM/ton
CFM
Watts
1343 / 1451
193 / 232
1352 / 1367
259 / 264
1355 / 1280
320 / 289
1353 / 1190
377 / 305
1346 / 1098
427 / 313
450
CFM/ton
CFM
Watts
1344
206
1352
270
1354
331
1352
387
1344
436
3.5 tons
290
CFM/ton
CFM
Watts
1034 / 1149
98 / 123
1041 / 1044
149 / 150
1038 / 934
197 / 170
1031 / 817
240 / 181
1018 / 690
279 / 182
290
CFM/ton
CFM
Watts
1034
103
1040
154
1037
202
1028
244
1014
281
350
CFM/ton
CFM
Watts
1228 / 1336
152 / 185
1235 / 1246
212 / 215
1236 / 1153
268 / 238
1232 / 1056
319 / 253
1224 / 955
365 / 259
350
CFM/ton
CFM
Watts
1229
162
1235
221
1236
276
1230
326
1220
371
400
CFM/ton
CFM
Watts
1389 / 1498
212 253
1399 / 1415
280 / 286
1403 / 1331
343 / 311
1401 / 1244
402 / 328
1395 / 1154
455 / 336
400
CFM/ton
CFM
Watts
1392
226
1400
293
1403
356
1400
413
1394
465
450
CFM/ton
CFM
Watts
1558 / 1669
290 / 343
1570 / 1592
367 / 377
1575 / 1514
439 / 404
1575 / 1434
505 / 422
1568 / 1351
563 / 432
450
CFM/ton
CFM
Watts
1561
310
1572
386
1576
457
1574
521
1567
577
4 tons †
290
CFM/ton
CFM
Watts
1168 / 1298
133 / 170
1175 / 1205
191 / 200
1175 / 1109
244 / 223
1170 / 1010
293 / 237
1160 / 905
336 / 242
290
CFM/ton
CFM
Watts
1168
141
1176
198
1174
251
1168
299
1157
341
350 †
CFM/ton
CFM
Watts
1389 / 1517
212 / 262
1399 / 1436
280 / 295
1403 / 1352
343 / 321
1401 / 1266
402 / 338
1395 / 1177
455 / 346
350
CFM/ton
CFM
Watts
1392
226
1400
293
1403
356
1400
413
1394
465
400
CFM/ton
CFM
Watts
1583 / 1714
303 / 370
1595 / 1639
382 / 546
1601 / 1562
455 / 431
1600 / 1483
521 / 450
1593 / 1401
580 / 459
400 †
CFM/ton
CFM
Watts
1586
325
1597
402
1601
474
1599
538
1591
595
450
CFM/ton
CFM
Watts
1790 / 1918
429 / 511
1800 / 1848
515 / 546
1808 / 1775
594 / 573
1793 / 1701
663 / 592
1698 / 1625
660 / 601
450
CFM/ton
CFM
Watts
1794
459
1801
544
1800
620
1766
665
1667
655
4.5 tons**
290
CFM/ton
CFM
Watts
1301 / 1429
177 / 222
1310 / 1344
241 / 253
1312 / 1256
300 / 278
1309 / 1165
355 / 294
1302 / 1071
404 / 302
290
CFM/ton
CFM
Watts
1302
189
1310
252
1311
310
1309
355
1301
403
350
CFM/ton
CFM
Watts
1558 / 1688
290 / 354
1570 / 1613
367 / 389
1575 / 1535
439 / 415
1575 / 1455
505 / 434
1568 / 1373
563 / 444
350
CFM/ton
CFM
Watts
1557
290
1570
367
1575
439
1575
505
1569
563
400
CFM/ton
CFM
Watts
1790 / 1918
429 / 511
1800 / 1848
515 / 546
1801 / 1775
594 / 573
1793 / 1701
663 / 592
1698 / 1625
660 / 601
400
CFM/ton
CFM
Watts
1789
428
1799
515
1801
594
1794
663
1701
659
450
CFM/ton
CFM
Watts
2018 / 2018
605 / 605
1973 / 1973
656 / 656
1857 / 1857
645 / 645
1749 / 1749
637 / 637
1651 / 1651
631 / 631
450
CFM/ton
CFM
Watts
2018
605
1975
656
1863
643
1757
634
1660
628
1. * Models start with "A" or "T"
2. † Factory Setting
3. ** Not an actual OD size
4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
5. Torque mode will reduce airflow when static is above approximately 0.4” water column.
6. If the air handler is applied in downflow or horizontal configurations, the
airflow should not exceed 2000 CFM. Airflow above 2000 CFM could result in
water blow-off.
7. All heating modes default to Constant CFM.
8. Cooling airflow values are with wet coil, no filter
MODEL NO.
BAYEVAC05BK1A
BAYEVAC05LG1AA
BAYEVAC08BK1A
BAYEVAC08LG1AA
BAYEVAC10BK1A
BAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA BAYEVCC25BK1AA
*AM8A0C48V41SA
A
1063/1188 1063/1500 1125/1500 1000/1188 1125/1563 1250/1625 1500/1750 1625/1813
WITHOUT HEAT PUMP / WITH HP
SEE AIR HANDLER NAMEPLATE
MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX
AM8A0C48 Minimum Heating Airflow Settings
NOTE: Minimum auxiliary heating airflow is automatically configured by the air
handler model and the auxiliary heater model number. This is not field adjustable.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Hyperion AAM8A0C48V41CA and is the answer not in the manual?

Trane Hyperion AAM8A0C48V41CA Specifications

General IconGeneral
BrandTrane
ModelHyperion AAM8A0C48V41CA
CategoryAir Handlers
LanguageEnglish

Related product manuals