SCXF-SVX01Q-EN
95
Figure 48. Evacuation time vs. pressure rise
200
400
600
800
1000
1200
1400
1600
-10 0 10 20 30 40 50 60 70 80 90
Pressure in Microns
Time in Minutes
Continously increasing pressure
indicates the presence of leaks,
moisture, or both.
Initial evacuation pressure.
State of equilibrium indicates the
true amount of moisture left in
the system. It indicates that no
leaks are present and the system
is properly evacuated.
State of equilibrium indicates the
true amount of moisture left in
the system. It indicates that no
leaks, but requires further evacuation.
Compressors
Scroll Compressor Failure Diagnosis and
Replacement
If compressor failure is suspected, refer to COM-SVN01
for detailed information regarding compressor failure
diagnosis and replacement of scroll compressors.