Installation
46 RT-SVX35H-EN
Figure 29. Customer connection wire range
Table 11. Electrical service sizing data for W_HE casings 2 - 9
Unit Component(s)
200/60/3, Nominal
(180-220V Utiliz.)
230/60/3, Nominal
(207-253V Utiliz.)
460/60/3, Nominal
(414-506V Utiliz.)
575/60/3, Nominal
(517-633V Utiliz.)
Electric Heat (WEHE Only): FLA (1) FLA (1) FLA (1) FLA (1)
30 Kw 83.3 72.2 36.1 28.9
50 Kw 138.8 120.3 60.1 48.1
70 Kw 194.3 168.4 84.2 67.4
90 Kw 249.8 216.5 108.3 86.6
110 Kw 305.3 264.6 132.3 105.9
130 Kw -n/a- -n/a- 156.4 125.1
150 Kw -n/a- -n/a- 180.4 144.3
170 Kw -n/a- -n/a- 204.5 163.6
190 Kw -n/a- -n/a- 228.5 182.8
Combustion Blower Motor
(WFHE Only): FLA FLA FLA FLA
235, 350, 500 MBh 2.1 1.8 0.9 0.7
850 & 1,000 MBh 2.8 2.4 1.2 1
Note: “Full load amp” values shown for the electric heat were determined at 480 and 600 volts, respectively.