System Start-up
RT-SVX35H-EN 85
Casing
Size
CFM Std
Air
Filters
Std Roof
Curb
Econ.with
or w/o
Exhaust
Fan
Throwaway
Perm Wire
Mesh
Bag &
Prefilter
Cartridge
&
PrefilterStd Fiber High Effic.
2
4000 .03 .03 .01 .3 .24 .01 .03
6000 .06 .06 .02 .5 .44 .02 .06
8000 .09 .09 .03 .71 .68 .05 .12
9000 .11 .11 .04 .83 .81 .07 .15
10000 .13 .13 .05 .95 .95 .10 .19
12000 .15 .15 .06 1.19 1.26 .14 .27
3
6000 .04 .04 .01 .34 .26 .02 .06
9000 .07 .07 .02 .54 .48 .07 .15
12000 .11 .11 .04 .75 .75 .16 .27
14000 .14 .14 .06 .95 .95 .25 .39
15000 .16 .16 .07 1.03 1.06 .30 .43
17000 .21 .21 .09 1.20 1.30 .39 .59
4
8000 .04 .04 .02 .37 .31 .01 .03
10000 .06 .06 .02 .49 .43 .02 .03
12000 .08 .08 .03 .61 .56 .04 .07
16000 .12 .12 .05 .88 .87 .10 .09
17000 .13 .13 .06 .95 .95 .12 .11
20000 .17 .17 .08 1.17 1.22 .19 .17
22000 .21 .21 .10 .23 .20
5
10000 .04 .04 .01 .37 .30 .03 .05
14000 .07 .07 .03 .56 .50 .07 .08
17000 .10 .10 .04 .72 .68 .12 .11
20000 .12 .12 .05 .88 .88 .19 .17
24000 .16 .16 .07 1.11 1.17 .30 .23
28000 .20 .20 .10 .39 .30
6
12000 .05 .05 .01 .44 .37 .02 .07
16000 .07 .07 .02 .63 .58 .05 .10
20000 .10 .10 .03 .84 .82 .10 .16
24000 .11 .11 .04 1.06 1.08 .16 .23
28000 .17 .17 .06 .30 .30
30000 .20 .20 .07 .34 .34
9
27000 .11 .13 N/A .68 .65 .20
32000 .14 .16 N/A .84 .84 .31
37000 .17 .19 N/A 1.02 1.04 .41
42000 .21 .22 N/A 1.19 1.06 .52
45000 .24 .24 N/A .63
46000 N/A .24 N/A .64
Notes:
1. Static pressure drops of accessory components must be added to external static pressure to enter fan selection tables.
2. Gas heat section maximum temperature rise of 60°F.
3. Throwaway filter option limited to 300 ft/min face velocity.
4. Bag filter option limited to 740 ft/min face velocity.
5. Horizontal roof curbs assume 0.50” static pressure drop or double the standard roof curb pressure drop, whichever is greater.
6. No additional pressure loss for model WXHE.
Table 21. Component static pressure drops (in. W.G.)

Table of Contents