kWh Counter [kWh]
Variable
name:
SNVT
type:
Value:
nvoDrvEnrg SNVT_elec_kwh_l
Min. Max. Resolution:
0 kWh 219,748,364.8 kWh 1 kWh
This variable contains the power consumption of the motor in kWh measured as a mean value over a one hour
period.
DC Link Voltage [V]
Variable
name:
SNVT
type:
Value:
nvoDCVoltage SNVT_volt
Min. Max. Resolution:
0 V 10,000 V 0.1 V
This variable contains the measured DC link voltage. The value is filtered and therefore may be delayed with up
to 1.3 seconds before a voltage change is reflected in the output variable.
Motor Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempMrt SNVT_lev_cont
Min. Max. Resolution:
0 % 100 % 0.5%
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempInvrtr SNVT_lev_cont
Min. Max. Resolution:
0 % 100 % 0.5%
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed-loop Feedback
Variable
name:
SNVT
type:
Value:
nvoFeedback SNVT_count_inc_f
Min. Max. Resolution:
0 % 100 % 0.5%
This variable contains the summarized amount of network feedback in closed-loop mode.
Configuration of the system