[ VII Microprocessor Control ]
- 13 -
HWE1832A GB
VII Microprocessor Control
[1] Microprocessor Control
1. Cool operation
1. Thermo regulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature + 2°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
(2) Anti-freezing control (Frost Prevention control of indoor unit)
Detected condition:
When BOTH conditions 1 and 2 have been meet, the indoor LEV will close to minimum Thermo OFF* position until released.
1) Indoor unit has been Thermo ON* in Cool/Dry mode for at least 16 min.
2) When the liquid pipe temp (TH22) or gas pipe temp (TH23) is 33.8°F or less, continuously for 3 min.
Released condition:
Anti-freezing control is cancelled when ANY one of the following conditions is satisfied, and an additional 3 minutes have
passed.
1) Liquid pipe temp (TH22) and gas pipe temp (TH23) are 50°F or above continuously for 1 min.
2) The condition of the Thermo OFF* has become complete by thermal-regulating (unit satisfies by set point).
3) The operation mode becomes a mode other than COOL or Dry.
4) The operation is stopped (unit is turned off).
5) Three min have passed from start of anti-freezing control.
*Thermo OFF = The IC coil is not actively cooling or heating.
*Thermo ON = The IC coil is actively cooling or heating.
Example:
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the [F1] button to display Cool.
3. Press the [F2] or [F3] button to set the desired temperature.
The set temperature changes 2°F when the [F2] or [F3] button is
pressed one time. Cooling 67 to 87°F
33.8°F
TH22
16 min after start cooling operation
3 min
4~6 min
Thermo OFF
Thermo ON
Thermo ON
Resume cooling operation
▪ [50°F or above (TH22 and TH23) for 1 min] and 3 min passed
or
▪ 6 min passed
33.8°F or less (TH22 or TH23) for 3 min

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Mitsubishi Electric TPEFYP024MA143A and is the answer not in the manual?

Trane Mitsubishi Electric TPEFYP024MA143A Specifications

General IconGeneral
BrandTrane
ModelMitsubishi Electric TPEFYP024MA143A
CategoryAir Conditioner
LanguageEnglish

Related product manuals