EasyManuals Logo

Trane NTXAMT A Series User Manual

Trane NTXAMT A Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
83
Check of LEV
No
Yes
No
Yes
Turn ON the power supply to the outdoor unit after checking LEV coil is
mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
Disconnect the connectors.
NTXMMX20A122AA NTXMPH20A122AA
CN791: LEV A, CN792: LEV B,
CN797: LEV R
OTHER MODELS
CN791: LEV A, CN792: LEV B, CN793: LEV C
CN794: LEV D (NTXMMX36A142AA/42A152AA),
CN795: LEV E (NTXMMX42A152AA),
Is there normal resistance to LEV coil?
(Refer to 11-5.)
Normal
Replace the outdoor control P.C. board.
Replace LEV coil.
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit gets warm.
CN791
CN792
CN793
CN794
CN795
CN797
Outdoor
control
P.C. board
OBHT702