SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment
can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
June 2022
SS-APG008H-EN
Application Guide
Split System Air Conditioners
Odyssey™
Tube Size and Component Selection
TTA and TWA (6-25 Tons)
(TTA Models)
TTA0724*A/D****B
TTA0904*A/D****B
TTA1204*C/D****B
TTA1504*D****B
TTA1804*C/D****B
TTA2404*C/D****B
TTA3004*C****B
(TWA Models)
TWA0724*A/D****B
TWA0904*A/D****B
TWA1204*A/D****B
TWA1804*D****B
TWA2404*D****B
Question and Answer IconNeed help?

Do you have a question about the Trane Odyssey TTA0724 A/D B Series and is the answer not in the manual?

Trane Odyssey TTA0724 A/D B Series Specifications

General IconGeneral
ModelTTA0724 A/D B Series
CategoryAir Conditioner
Cooling Capacity72, 000 BTU/h
TypeSplit System
Voltage208-230V
Phase3
Compressor TypeScroll
RefrigerantR-410A
Energy Efficiency Ratio (EER)11.0

Summary

Introduction

Warnings, Cautions, and Notices

Defines advisory types: warning, caution, and notice for safety.

Important Environmental Concerns

Discusses impact of chemicals on the ozone layer.

Important Responsible Refrigerant Practices

Emphasizes certified technicians and adherence to regulations.

Proper Field Wiring and Grounding

Stresses qualified personnel and code compliance for safety.

Personal Protective Equipment (PPE)

Details necessary PPE for hazardous operations.

Copyright

Trademarks

Revision History

Overview

Background

Explains the four major components of a split AC system.

Updated Guidelines

Introduces revised practices for refrigerant lines.

Liquid Lines

Discusses historical and current practices for liquid line sizing.

Suction Lines

Details sizing requirements for R-410A refrigerant suction lines.

Equipment Placement

Discusses optimal placement of components to minimize charge.

Refrigerant Piping Guidelines

Provides charts for allowable elevation difference based on line length.

Line Sizing, Routing, and Component Selection

Liquid Lines

Covers sizing, routing, insulation, and components for liquid lines.

Gas Line

Details line sizing and routing for gas lines.

DETINT

Explains the function of the DETINT for oil migration prevention.

Avoid Underground Refrigerant Lines

Warns against risks associated with underground refrigerant lines.

Insulation

Advises on insulating gas lines to prevent heat gain.

Components

Discusses adding gas line filters and access ports.

Access Port

Describes the purpose of access ports in gas lines.

Expansion Valve

Explains selection criteria for expansion valves based on system needs.

Check Valves

Details requirements and warnings for check valve installation.

Expansion Valves

TXV Selection and Superheat

Guides TXV selection for capacity and setting superheat.

Controls

System Stability Requirements

Details 5-minute intervals for compressor staging and stability.

Hot Gas Bypass

HGBP Overview

Discusses the history and impact of hot gas bypass.

Frostat Coil Frost Protection

Explains Frostat system's role in preventing coil freezing.

Additional Resources

Points to further information on HGBP.

Remodel, Retrofit, or Replacement

R-410A Upgrade Considerations

Outlines system changes needed for R-410A conversion.

Equipment Compatibility

Stresses compatibility of all components with R-410A and POE oil.

Equipment Damage Warning

Warns about using POE oil and potential damage from moisture.

Microchannel Heat Exchanger Condensers (MCHE)

MCHE Design and Function

Describes MCHE design and its impact on refrigerant charge.

Prohibited Practices

Lists practices to avoid with MCHE to prevent high pressure trips.

Refrigerant Piping Examples

TTA Cooling-Only Piping

Illustrates piping for TTA cooling-only units with TWE air handlers.

TTA Cooling-Only with Matched Coil

Shows typical piping for TTA cooling-only units with matched indoor coils.

TWA Heat Pump Piping

Depicts typical piping for TWA heat pumps with TWE air handlers.

TWA Heat Pump with Matched Coil

Illustrates typical piping for TWA heat pumps with matched indoor coils.

Indoor Coil with Single Distributor

Shows piping for single-circuit TTA/TWA units with one distributor.

Indoor Coil with Two Distributors

Details piping for single-circuit TTA/TWA units with two distributors.

Indoor Coil with Two Distributors (Dual-Circuit)

Illustrates piping for dual-circuit TTA/TWA units with two distributors.

Evaporator Coil with Four Distributors

Shows piping for evaporator coils with four distributors.

Indoor Coil with Four Distributors (Dual-Circuit)

Depicts piping for dual-circuit units with four distributors.

Parts

TTA Cooling Component Selection

Lists component selections for TTA cooling microchannel units (6-25 tons).

TWA Heat Pump Component Selection

Lists component selections for TWA heat pump units (6-20 tons).

Expansion Valves

Provides a table of expansion valves for TTA/TWA applications.

R-410A lbs Charge per 100 ft

Details R-410A refrigerant charge per 100 ft for various OD sizes.