DEFINITION:
Ground Fault - Incoming or chassis
ground connec!on is not sensed
Connect volt meter
to black incoming
and chassis ground
Does meter read
~120 vac?
Disconnect incoming
electrical power to
modular blower
NO
Correct earth ground.
Check opera!on
Modular blower must be
dedicated circuit.
Check / correct all ground
connec!ons within modular blower
for con!nuity. Modular blower
dedicated circuit.
Disconnect incoming
electrical power to
modular blower
YES
Check opera!on
06 Fault Code
Faulty Ground
on a
be on a must
TTrroouubblleesshhoooottiinngg