Trane P0V0B000M40SDA - Serial Motor Troubleshooting

Trane P0V0B000M40SDA
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
P0V0-SVX001-1A-EN
Is ~12VDC measured
from terminals 1 (12V)
and 3 (GND) at the
IMBC?
NO
Replace IMBC
Check opera!on
Is 120 VAC measured at
the line voltage connector
at the motor? (5 pin
connector terminals 4 and
5)
Correct, replace wiring.
Check opera!on
NO
YES
Remove the serial
motor wiring
harness at the IMBC.
Apply 24 VAC to
wires 3 & 4.
Does motor run?
Replace motor.
Check opera!on
NO
Replace IMBC. Check
opera!on
YES
See diagram #2 below
#4 = WHITE wire, connects to TX
#3 = BLACK wire, connects to GND
Serial Motor
Troubleshoo!ng
See diagram #1 below
DIAGRAM #1
DIAGRAM #2