Periodic Maintenance
Check the refrigerant charge and oil level. Refer to Paragraphs "Weekly
Maintenance" on Page 133 and "Oil Separator Level Check" on Page 139.
Routine changing of oil is not required.
Have a qualified laboratory perform a compressor oil analysis to deter-
mine system moisture content and acid level. This analysis is a valuable
diagnostic tool.
Check the pressure drop across the oil filter. See Paragraph "Oil Filter
Change" on Page 140.
Contact a qualified service organization to leak test the chiller, to check
operating and safety controls, and to inspect electrical components for
deficiencies.
Inspect all piping components for leakage and damage. Clean out any
inline strainers.
Clean and repaint any areas that show signs of corrosion.