EasyManua.ls Logo

Trane RAUC-IOM-15 - Page 15

Trane RAUC-IOM-15
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Installation (Continued)
Table 3-1A
Typical Unit Weights & Point Loading Data
Unit Fin Operating Unit Weight on Isolator @ Mounting Location
Size Material Weight Location 1 2345678
C80 AL 5500 855 557 835 544 830 541 810 528
CU 6099 926 629 909 618 906 616 890 605
D10 AL 6472 1010 656 983 639 979 636 951 618
CU 7272 1104 752 1083 738 1080 736 1058 721
D12 AL 7000 1100 694 1075 678 1071 676 1046 660
CU 8199 1241 838 1225 827 1222 825 1206 815
Note:
1. Mountin
g
locations correlate with those shown in point loadin
g
illustration.
Table 3-1B
Typical EVP Chiller Weights & General Data
Chiller Shipping Operating No. of Ref. Capacity Refrigerant Tube Pull
Size Weight Weight Circuits (Gallons) Charge (Lbs.)* (inches)**
80 Ton 875 1,205 2 43.1 26.5 95
100 Ton 960 1,230 2 35.0 33.4 95
120 Ton 1,150 1,535 2 47.9 40.4 95
* - Refrigerant change is approximate and for the evaporator chiller only.
** - Tube Pull
g
iven is the len
g
th of the evaporator.
Figure 3-3
Rigging and Center-of-Gravity Data
Location of Center of
Shipping Gravity =
Unit Weight X Z
Size (Max. Lbs) In mm In mm
C80 5995 79.1 2009 34.5 876.3
D10 7160 104.2 2647 34.6 878.8
D12 8052 104.7 2659 34.4 873.8
LIFTING AND MOVING INSTRUCTIONS!
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS
SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT
UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE
SAME LENGTH. ADJUST AS NECESSARY FOR EVEN
LEVEL LIFT.
USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER
TO INSTALLATION MANUAL OR NAMEPLATE FOR UNIT
WEIGHT. REFER TO INSTALLATION INSTRUCTIONS
LOCATED INSIDE CONTROL PANEL FOR FURTHER
RIGGING INFORMATION.

Table of Contents