30
Table 3-5
Electrical Service Sizing Data
Allowable Minimum Maximum Recommended
Electrical Voltage Circuit Overcurreent Dual Element KW FLA LRA
Model Characteristics Range Ampacit
y
Protecton Fuse Size (Ea) No HP (Ea) (Ea)
200/60/3XL 180-220 373 400 400 0.90 8 1.0 4.1 20.7
RAUC-C80 230/60/3XL 208-254 373 400 400 0.90 8 1.0 4.1 20.7
460/60/3XL 416-508 162 175 175 0.90 8 1.0 1.8 9.0
575/60/3XL 520-635 129 150 150 0.90 8 1.0 1.4 7.2
200/60/3XL 180-220 472 500 500 0.90 12 1.0 4.1 20.7
RAUC-D10 230/60/3XL 208-254 472 500 500 0.90 12 1.0 4.1 20.7
460/60/3XL 416-508 206 225 225 0.90 12 1.0 1.8 9.0
575/60/3XL 520-635 164 175 175 0.90 12 1.0 1.4 7.2
200/60/3XL 180-220 548 600 600 0.90 12 1.0 4.1 20.7
RAUC-D12 230/60/3XL 208-254 548 600 600 0.90 12 1.0 4.1 20.7
460/60/3XL 416-508 239 250 250 0.90 12 1.0 1.8 9.0
575/60/3XL 520-635 190 200 200 0.90 12 1.0 1.4 7.2
Unit Characteristics Condenser Fan Motor
RLA RLA LRA LRA Kw Kw
No. (Ea) (Ea) (Ea) (Ea) (Ea) (Ea)
10/15 10 Ton 15 Ton 10 Ton 15 Ton 10 Ton 15 Ton
41.4 60.5 269.0 409.0 10.99 16.48
2/4 41.4 60.5 251.0 376.0 10.99 16.48
18.1 26.3 117.0 178.0 10.99 16.48
14.4 21.0 94.0 143.0 10.99 16.48
41.4 60.5 269.0 409.0 11.09 16.64
4/4 41.4 60.5 251.0 376.0 11.09 16.64
18.1 26.3 117.0 178.0 11.09 16.64
14.4 21.0 94.0 143.0 11.09 16.64
60.5 409.0 16.43
4/4 60.5 376.0 16.43
26.3 178.0 16.43
21.0 143.0 16.43
Compressor Motor
Notes :
1. Electrical data is for each individual motor.
2. Maximum Overcurrent Protection device permitted by N.E.C. 440-22 (1993) is 225% of the largest compressor motor RLA
plus the remaining motor RLA and FLA values.
3. Minimum circuit ampacity is 125% of the largest compressor motor RLA plus the remaining motor RLA and FLA values.
4. Recommended dual element fuse size is 150% of the lar
g
est com
p
ressor motor RLA
p
lus the remainin
g
motor RLA and FLA values.
5. Kw values are taken at conditions of 45
o
F saturated suction tem
p
erature at the com
p
ressor and 95
o
F ambient.
6. Local codes may take precedence.