General start-up
Check fi xing of capillary tubes (protection from vibration and from wear) and insure that they are not damaged.
Reset all manually set control devices.
Check refrigerating circuits tightness.
Check oil acidity.
Check electrical terminals tightening of the motors and in the control panel.
Check the isolation of the motors using a 500V DC megohmeter which meets manufacturers specifi cations
(minimum value 2 megohms).
Check the direction of the rotation using phasemeter.
Electrical power wiring:
Check all the electrical terminals tightening.
Set-up compressors overload relays.
Set-up fan-motors overload relays.
Electrical control wiring:
Check all the electrical terminals tightening.
Check all the pressostats.
Check and set-up the control module.
Test and start-up without the electrical power.
Condenser:
Check setting of the safety pressure valve.
Check direction of the rotation of fans.
Check the isolation of the motors using a 500V DC megohmeter which meets manufacturers specifi cations
(minimum value 2 megohms).
Operating parameters statement:
Switch on main power supply switch.
Start-up the unit by pushing auto on the control module screen.
After unit start up, leave in operation for at least 15 minutes, to insure pressures are stabilized.
Then check:
voltage.
compressors and fan-motors currents.
suction temperature and pressure.
ambient air temperature.
blowing air temperature.
discharge pressure and temperature.
liquid refrigerant temperature and pressure.
operating parameters:
superheat: difference between suction temperature and dew point temperature. Normal superheat must be within
5°C and 10°C.
sub-cooling: difference between liquid temperature and bubble point temperature. Normal sub-cooling on
standard unit with R134a should be 5 to 10°C, and 2 to 5°C with 407c.
difference between dew point temperature in high pressure and condenser air inlet temperature. Normal value on
standard unit with R134a and all the fans operating should be 15 to 18°C. With 407C, it should be 20 to 23°C.
Final check:
When the unit is operating correctly:
Check that the unit is clean and clear of any debris, tools, etc…
All valves are in operating position.
Close control and starter panel doors and check panels fi xation.