MCA = Minimum circuit ampacity = 125% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.
2
Maximum fuse size = 225% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.