91 RTAC-SVX002A-EN
Diagnostics
Hex
Code
Diagnostic Name and
Source
Severity Persistence Criteria Reset Level
1ED Starter Fault Type II –
Compressor 1A
Immediate Latch a. This is a specic starter test where the Shorting Contactor (1K3) is
individually energized and a check is made to ensure that there are
no currents detected by the CT's. If current is detected when only S is
energized at Start, then 1M is shorted. b. This test in a. above applies
to all forms of starters (Note: It is understood that many starters do not
connect to the Shorting Contactor.).
Local
1EE Starter Fault Type II –
Compressor 1B
Immediate Latch Same as Starter Fault Type II - Compressor 1A Local
1EF Starter Fault Type II –
Compressor 2A
Immediate Latch Same as Starter Fault Type II - Compressor 1A Local
1F0 Starter Fault Type II –
Compressor 2B
Immediate Latch Same as Starter Fault Type II - Compressor 1A Local
1F1 Starter Fault Type III –
Compressor 1A
Immediate Latch As part of the normal start sequence to apply power to the compressor,
the Shorting Contactor (1K3) and then the Main Contactor (1 K1) were
energized. 1.6 seconds later there were no currents detected by the
CT's for the last 1.2 Seconds on all three phases. The test above
applies to all forms of starters except Adaptive Frequency Drives.
Local
1F2 Starter Fault Type III –
Compressor 1B
Immediate Latch Same as Starter Fault Type III - Compressor 1A Local
1F3 Starter Fault Type III –
Compressor 2A
Immediate Latch Same as Starter Fault Type III - Compressor 1A Local
1F4 Starter Fault Type III –
Compressor 2B
Immediate Latch Same as Starter Fault Type III - Compressor 1A Local
5C7 Starter Module Memory Error
Type 1 - Starter 2A
Info Latch Checksum on RAM copy of the Starter LLID conguration failed.
Conguration recalled from EEPROM.
Local
5C8 Starter Module Memory Error
Type 1 - Starter 2B
Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5C5 Starter Module Memory Error
Type 1Starter 1A
Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5C6 Starter Module Memory Error
Type 1-Starter 1B
Info Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5C9 Starter Module Memory Error
Type 2 - Starter 1A
Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5CA Starter Module Memory Error
Type 2 - Starter 1B
Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5CB Starter Module Memory Error
Type 2 - Starter 2A
Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
5CC Starter Module Memory Error
Type 2 - Starter 2B
Immediate Latch Same as Starter Module Memory Error Type 1 - Starter 2A Local
6B1 Starter Panel High
Temperature Limit – Panel 1,
Cprsr 1B
Special
Mode
NonLatch Starter Panel High Limit Thermostat (170°F) trip was detected.
Note: Other diagnostics that may occur as an expected consequence
of the Panel High Temp Limit trip will be suppressed from annunciation.
These include Phase Loss, Power Loss, and Transition Complete
Input Open for Cprsr 1B
Local
6B0 Starter Panel High
Temperature Limit – Panel 1,
Cprsr 2A
Special
Mode
NonLatch Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B Local
6B2 Starter Panel High
Temperature Limit – Panel 2,
Cprsr 2B
Special
Model
NonLatch Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B Local
5BA Suction Refrigerant Pressure
Transducer – Circuit 1,
Compressor 1A
Immediate Latch Bad Sensor or LLID Circuit target if no isolation valves, Compressor
target if isolation valves. Design Note: In the case of manifolded
compressors w/o isolation valves, the occurrence of this diagnostic
will also generate a comm loss with the nonexistent Suction Press
Cprsr 1B in order to accomplish circuit shutdown.
Remote
5BB Suction Refrigerant Pressure
Transducer – Circuit 1,
Compressor 1B
Immediate Latch Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Remote
5BC Suction Refrigerant Pressure
Transducer - Circuit 2,
Compressor 2A
Immediate Latch Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Remote
5BD Suction Refrigerant Pressure
Transducer - Circuit 2,
Compressor 2B
Immediate Latch Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Remote