Temperature Sensors
RTHC-SVD01B-EN 17
16. A decade box or resistor can be substituted for the sensor and
any sensor table value used to relate the resistance to the tem-
perature. By removing the Phoenix connector plug and applying
the resistance to the proper pin terminals, the temperature, as
sensed by UCP2, can be confirmed. Use the CLD to confirm that
the input of the decade box or resistor matches the resistance
tables.