EasyManua.ls Logo

Trane RTHC - Page 42

Trane RTHC
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Under-Over Voltage Transformer
36 RTHC-SVD01B-EN
The ratio of the primary or line voltage to the open circuity secondary
voltage should be 20 to 1. If the unloaded turns ratio is not within 2% of
this value, replace the transformer.
Reconnect the secondary back to J3 and re-measure the loaded (con-
nected) secondary voltage. The new loaded ratio should be approxi-
mately 20.2 to 1. If not within 2% of this ratio, the transformer's
secondary should be disconnected from the Starter module and a 1
kOhm resistor connected across the secondary. Measuring the voltage
across the 1 kOhm resistor should yield a voltage ratio of 20.17. Ratios
more than ±2% in error suggest a bad transformer. If the 1 kOhm
loaded ratio is within tolerance, but the UCP2 connected ratio is out of
tolerance, suspect a bad Starter module. Before replacing the Starter
module, double check the Unit Line Voltage programed in the Machine
Configuration Menu under Service Settings. It should match the name-
plate unit line voltage.
If the Under-Over Voltage Protection function continues to trip the unit,
and all of the above measured ratios are within tolerance, and all CLD
Under-Over Voltage setups have been verified, replace the Starter
module.

Other manuals for Trane RTHC

Related product manuals