Module Power and Miscellaneous I/O
RTHC-SVD01B-EN 81
The DC voltages shall be within the following tolerances. If not, replace
the module.
13-7 b. I/O Terminals
For the checkout of the I/O, refer to the Chiller Wiring Diagrams for
both high and low voltage circuits. All voltages are measured between
terminal pairs specified unless otherwise indicated. Nominal voltages
are given and may vary by +
5%. Unregulated voltages (unreg) or 115
VAC voltages may vary by +
15%.
Table 13-8: Test Point Voltages for 1U5 Module
Test Point Voltage (VDC)
TP1 4.8 to 5.2
TP2 23 to 25