RLC-SVX14H-GB
48
Table 16 - RTWD High Seasonal Effi ciency R134a (Continued)
Unit size 100 100 100 110 110 110 120 120 120 130 130 130
Unit Type Digit 12 2 2 2 2 2 2 2 2 2 2 2 2
Unit Application Digit 15 A A B;C A A B;C A A B;C A A B;C
Evap Application Digit 21 1 2;3 * 1 2;3 * 1 2;3 * 1 2;3 *
Comp Starter digit 24 B B B B B B B B B B B B
Compressor C1 L1 LoVi L1 HiVi L1 HiVi L2 LoVi L2 HiVi L2 HiVi L2 LoVi L2 HiVi L2 HiVi M1 LoVi M1 HiVi M1 HiVi
C2 L2 LoVi L2 HiVi L2 HiVi L2 LoVi L2 HiVi L2 HiVi M1 LoVi M1 HiVi M1 HiVi M1 LoVi M1 HiVi M1 HiVi
Circuit 1 Motor RLA (A) 60.0 60.0 77.6 72.0 72.0 92.8 72.0 72.0 92.8 84.8 84.8 112.8
Motor LRA (A) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Max Amps (A) 64.3 64.3 93.2 71.3 71.3 109.6 71.3 71.3 109.6 85.0 85.0 129.1
Max Power input (kW) 42.3 42.3 61.3 46.9 46.9 72.1 46.9 46.9 72.1 56.0 56.0 85.0
Circuit 2 Motor RLA (A) 72.0 72.0 92.8 72.0 72.0 92.8 84.8 84.8 112.8 84.8 84.8 112.8
Motor LRA (A) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Max Amps (A) 71.3 71.3 109.6 71.3 71.3 109.6 85.0 85.0 129.1 85.0 85.0 129.1
Max Power input (kW) 46.9 46.9 72.1 46.9 46.9 72.1 56.0 56.0 85.0 56.0 56.0 85.0
Unit @ Max Starting Amps (A) 137.6 137.6 204.8 144.6 144.6 221.2 158.3 158.3 240.8 172.0 172.0 260.3
Amps ctl + auxiliaires 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Max. Amps (A) 137.6 137.6 204.8 144.6 144.6 221.2 158.3 158.3 240.8 172.0 172.0 260.3
displacement power
factor (DPF)
0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950 0.950
short circuit withstand
rating (kA)
35 35 35 35 35 35 35 35 35 35 35 35
Disconnect
Switch
Digit 26=C
Fuse size (A) C1 80 gG-T0080 gG-T00 125 gG-
T00
125 gG-
T00
125 gG-
T00
160 gG-
T00
125 gG-
T00
125 gG-
T00
200 gG-T1160 gG-T1160 gG-T1200 gG-T1
Fuse size (A) C2 100 gG-
T00
100 gG-
T00
160 gG-
T00
125 gG-
T00
125 gG-
T00
160 gG-
T00
160 gG-
T00
160 gG-
T00
200 gG-T1160 gG-T1160 gG-T1200 gG-T1
Disconect Switch Size 6X160A -
T00
6X160A -
T00
6X160A -
T00
6X160A -
T00
6X160A -
T00
6X160A -
T00
6X160A -
T00
6X160A -
T00
6X250A -
T1
6X250A -
T1
6X250A -
T1
6X250A -
T1
Max connecting Wire
(mm²)
2 x 95 2 x 95 2 x 95 2 x 95 2 x 95 2 x 95 2 x 95 2 x 95 2 x 185 2 x 185 2 x 185 2 x 185
Bus bar width (mm) 20 20 20 20 20 20 20 20 32 32 32 32
Circuit Breaker +
Bus bar
Digit 26=D
circuit breaker size
(A) C1
NSX 100A NSX 100A NSX 160A NSX 100A NSX 100A NSX 160A NSX 100A NSX 100A NSX 160A NSX 160A NSX 160A NSX 160A
circuit breaker size
(A) C2
NSX 100A NSX 100A NSX 160A NSX 100A NSX 100A NSX 160A NSX 160A NSX 160A NSX 160A NSX 160A NSX 160A NSX 160A
Bus bar connection Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Copper
bar 50x8
Max connecting Wire
(mm²)
2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240 2 x 240