18-GJ06D2-2A
Dip Switches
Scan to see a
video on setting
the TAM7 DIP
Switches.
Click or Scan to see a video on setting the
TAM7 DIP Switches
DDiipp SSwwiittcchh SS11
Set the S1–1 and S1–2 dip switches for the OD
multiplier (tonnage) per the chart.
INDOOR MODEL S1–1 S1–2 OD MULTIPLIER
TAM7A0A24H21SC
OFF OFF 2
OFF ON 1.5
ON OFF 2.5
ON ON 3
TAM7A0B30H21SC
OFF OFF 2
OFF ON 1.5
ON OFF 2.5
ON ON 3
TAM7A0C36H31SC
OFF OFF 3
OFF ON 2
ON OFF 2.5
ON ON 3.5
TAM7A0C42H31SC
OFF OFF 3.5
OFF ON 2.5
ON OFF 3
ON ON 4
TAM7A0C48H41SC
OFF OFF 4
OFF ON 3
ON OFF 3.5
ON ON 4.5**
TAM7B0C60H51SB
OFF OFF 4.5**
OFF ON 3.5
ON OFF 4
ON ON 5
NNoottee:: The OD multiplier in conjunction with the CFM/
TON can be used to adjust total airflow for your
application.
Example: 4.5T x 370 CFM/TON = 1665 CFM
** Not an actual OD size
Set the S1–3 dip switch for AC or HP.
OD TYPE S1–3
HP OFF
AC ON
1
1
1 2 3 4 5
1 2 3 4 5
HP
2 (Comp res sor)
2 (Stag es )
AC (Sys tem)
}
OUTDOOR
Capa city (Tons )
OUTDOOR
}
Torque
CFM/Ton
Coo l Off Delay
}
INDOOR
CFM
+12V
R13
R14
R4
U1
R NET 1
S1
on
on
S2
R NET 2
R
6
C22
C19
C10
D9
1
Airflow Control (AFC)
S1
Set the S1–4 dip switch for the number of stages on
the outdoor unit.
OD STAGES S1–4
1 OFF
2 ON
NNoottee:: Refer to the field wiring diagram of the Outdoor
Unit to determine if the unit is 1 or 2 stage.
NNoottee:: This dip switch should be changed while the
power is off or no demand is present. The power
must be shut off and then re-applied in order for
the AFC to recognize the change.
Set the S1–5 dip switch for the number of
compressors.
# COMPRESSORS S1–5
1 OFF
2 ON