ELECTRONIC HEAT PUMP THERMOSTAT
Pub. No. 11-HD28D2-1
Table 2. Thermostat Installer Setup Options (Continued).
Installer
Setup Number
Factory-Setting
Other Choices
(Press ▲ or ▼ key to change)
Select Display Description Display Description
Degree temperature
display
14 00 Temperature displays in
°F
01 Temperature displays in °C
Extended fan operation in
heating
19 00 No extended fan
operation after the call
for heat ends
01, 02
or 03
01—Fan operation exends
30 seconds after the call
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
Extended fan operation in
cooling
20 00 No extended fan
operation after the call
for cool ends
01, 02
or 03
01—Fan operation exends
30 seconds after the call
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
Outdoor temperature
display (select models)
24 00 No outdoor temperature
displays.
01 Outdoor temperature is
displayed. Needs a
TAYSENS100A Outdoor
Sensor
Comfort-R Enable 28 00 No fan delay 01 or
02
01—30 seconds (maximum
delay)
02—15 seconds (maximum
delay)
Minimum deadband
between heating and
cooling in auto
changeover mode
30 04 Heating and cooling
setpoints can be set no
closer than 4°F (2°C)
03 thru
10
Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3°F (1.5°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Minimum on time (heat) 32 10 Ten-minute minimum on
time for compressor
(heating)
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
on during call for heat
Minimum on time
(cooling)
33 10 Ten-minute minimum on
time for compressor
(cooling)
00 thru
15
Minimum number of minutes