2-17 Over-voltage Control
Option: Function:
Select whether to enable OVC during ramp
down, which reduces the risk of frequency
converter trip due to overvoltage on the DC
link caused by generative power from load.
[0] Disabled No OVC required.
[1] Enabled (not
at stop)
Activates OVC when the frequency converter
is not in the stop state.
[2]
*
Enabled Activates OVC.
NOTICE
The ramp time is automatically
adjusted to avoid tripping of the
frequency converter.
Parameters TR150 and TR170