3Parameters
The * in parameter numbers indicates a group or subgroup
of parameters for which the rst 1 or 2 numbers are the
same. For example, 0-** indicate the group of parameters
that all start with 0. 0-0* indicates the subgroup of
parameters that share the rst 2 numbers, which is 0-0.
An asterisk (*) after an option number indicates it is the
default option. For example, [0]* English is the default
option for parameter 0-01 Language.
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the keypad keys, and
conguration of the keypad display.
3.1.1 0-0* Basic Settings
0-01 Language
Option: Function:
Denes the language to be used in the
display.
[0]
*
English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
[28] Bras.port
[255] Numeric prg.
0-03 Regional Settings
Option: Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
To meet the needs for
dierent
default settings
in
dierent
parts of the world,
parameter 0-03 Regional Settings is implemented
in the frequency converter. The selected setting
inuences
the default setting of the motor
nominal frequency.
[0]
*
Interna-
tional
Sets the default value of parameter 1-23 Motor
Frequency to 50 Hz.
[1] North
America
Sets the default value of parameter 1-23 Motor
Frequency to 60 Hz.
0-04 Operating State at Power-up
Option: Function:
Select the operating mode after reconnection of
the frequency converter to mains voltage after
power-down when operating in Hand (local)
mode.
[0]
*
Resume Resumes operation of the frequency converter,
maintaining the same local reference and the
same start/stop condition (applied by [Hand
On]/[O] on the keypad or local start via a
digital input as before the frequency converter
was powered down.
[1] Forced
stop,
ref=old
Uses saved reference [1] to stop the frequency
converter, but at the same time retains the local
speed reference in memory before powering
down. After mains voltage is reconnected, and
after receiving a start command (pressing [Hand
On] key or using the local start command via a
digital input), the frequency converter restarts
and operates at the retained speed reference.
0-06 GridType
Option: Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all options are supported
in all power sizes.
IT Grid is a supply mains, where
there are no connections to
ground.
Delta is a supply mains where the
secondary part of the transformer
is delta connected and 1 phase is
connected to ground.
[0] 200-240V/50Hz/IT-grid
[1] 200-240V/50Hz/Delta
[2] 200-240V/50Hz
[10] 380-440V/50Hz/IT-grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-grid
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[30] 525-600V/50Hz/IT-grid
[31] 525-600V/50Hz/Delta
[32] 525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 25
3
3