EasyManua.ls Logo

Trane TR150 - Page 50

Trane TR150
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital input
function
Description
[64] Counter B (down) Input for decrement counting in the SLC
counter.
[65] Reset Counter B Input for reset of counter B.
[101] Sleep A signal applied puts the frequency
converter into sleep mode.
Table 3.3 Digital Input Functions
Selected
preset
reference:
Preset
reference bit 2
Preset
reference bit 1
Preset
reference bit 0
Preset
reference 0
000
Preset
reference 1
001
Preset
reference 2
010
Preset
reference 3
011
Preset
reference 4
100
Preset
reference 5
101
Preset
reference 6
110
Preset
reference 7
111
Table 3.4 Selected Preset Reference
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8]
*
Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
5-11 Terminal 19 Digital Input
Parameter for conguring the input function on input terminal
19.
Option: Function:
[0]
*
No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 49
3
3

Table of Contents

Other manuals for Trane TR150