8-54 Reversing Select
Option: Function:
[2] Logic
AND
Activates a reverse command via the serial
communication port, and via 1 of the digital
inputs.
[3] Logic
OR
Activates a reverse command via the serial
communication port or via 1 of the digital inputs.
8-55 Set-up Select
Option: Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port.
[2] Logic
AND
Activates the set-up selection via the serial
communication port, and via 1 of the digital
inputs.
[3]
*
Logic
OR
Activate the set-up selection via the serial
communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter preset
reference selection via the terminals (digital
input) and/or via the serial communication port.
[0] Digital
input
Activates the preset reference selection via a
digital input.
[1] Bus Activates the preset reference selection via the
serial communication port.
[2] Logic
AND
Activates the preset reference selection via the
serial communication port, and via 1 of the
digital inputs.
[3]
*
Logic OR Activates the preset reference selection via the
serial communication port or via 1 of the digital
inputs.
3.8.5 8-7* BACnet
8-70 BACnet Device Instance
Range: Function:
1
*
[0 - 4194303 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range: Function:
127
*
[0 - 127 ] Dene the address of the master, which holds
the highest address in this network. Decreasing
this value optimizes polling for the token.
8-73 MS/TP Max Info Frames
Range: Function:
1
*
[1 - 65534 ] Dene how many info/data frames the device
is allowed to send while holding the token.
8-74 "I am" Service
Option: Function:
[0]
*
Send at
power-up
Select when the device should send the I-
Am service message only at power-up.
[1] Continuously Select when the device should send the I-
Am service message continuously with an
interval of approximately 1 minute.
8-75 Intialisation Password
Range: Function:
admin
*
[1 - 1 ] Enter the password needed for execution of
Drive Re-initialization from BACnet.
8-79 Protocol Firmware version
Array[5]
Range: Function:
Size
related
*
[0 -
65535 ]
Firmware revision of frequency
converter is in index 0, Modbus is in
index 1, Metasys N2 is in index 2, FLN
is in index 3, BACnet is in index 4.
3.8.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the Drive port.
8-80 Bus Message Count
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
valid telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
telegrams with faults (for example, CRC
fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0
*
[0 - 4294967295 ] This parameter shows the number of
valid telegrams addressed to the slave,
sent by the frequency converter.
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 63