16-12 Motor Voltage
Range: Function:
0 V
*
[0 - 65535 V] View the motor voltage, a calculated value
used for controlling the motor.
16-13 Frequency
Range: Function:
0 Hz
*
[0 - 6553.5 Hz] View the motor frequency, without
resonance damping.
16-14 Motor current
Range: Function:
0 A
*
[0 - 655.35 A] View the motor current measured as an
average value, I
RMS
.
16-15 Frequency [%]
Range: Function:
0 %
*
[0 -
6553.5 %]
View a 2-byte word reporting the actual
motor frequency (without resonance
damping) as a percentage (scale 0000–4000
hex) of parameter 4-19 Max Output
Frequency.
16-16 Torque [Nm]
Range: Function:
0 Nm
*
[-30000 -
30000 Nm]
View the torque value that is applied on
the motor shaft. Some motors supply more
than 160% torque. Consequently, the
minimum value and the maximum value
depends on the minimum/maximum motor
current as well as the motor used.
16-17 Speed [RPM]
Range: Function:
0 RPM
*
[-30000 -
30000 RPM]
View the actual motor RPM. The motor
RPM is estimated in open-loop process or
closed-loop process control modes and
the motor RPM is measured in speed
closed-loop mode.
16-18 Motor Thermal
Range: Function:
0 %
*
[0 -
100 %]
View the calculated motor temperature in
percentage of allowed maximum. At 100%, a trip
occurs if selected in parameter 1-90 Motor
Thermal Protection. The basis for the calculation
is the ETR function selected in
parameter 1-90 Motor Thermal Protection.
16-22 Torque [%]
Range: Function:
0 %
*
[-200 -
200 %]
View the torque in percentage (in relation
to the nominal torque) that is applied to
the motor shaft.
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range: Function:
0 V
*
[0 - 65535 V] Shows the actual DC-link voltage.
16-34 Heatsink Temp.
Range: Function:
0 °C
*
[-128 - 127 °C] View the heat sink temperature of the
frequency converter.
16-35 Inverter Thermal
Range: Function:
0 %
*
[0 - 255 %] View the percentage of thermal load on the
frequency converter. At 100%, a trip occurs.
16-36 Inv. Nom. Current
Range: Function:
0 A
*
[0 - 655.35 A] View the inverter nominal current. The data
is used for motor overload protection, and
so on.
16-37 Inv. Max. Current
Range: Function:
0 A
*
[0 - 655.35 A] View the inverter maximum current. The
data is used for calculation of frequency
converter protection, and so on.
16-38 SL Controller State
Range: Function:
0
*
[0 - 20 ] View the actual state of the smart logic controller
(SLC).
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range: Function:
0 %
*
[-200 - 200 %] View the total reference, the sum of
digital, analog, preset, bus, and freeze
references.
16-52 Feedback[Unit]
Range: Function:
0
ProcessCtrlUnit
*
[-4999 - 4999
ProcessCtrlUnit]
View the feedback resulting
from the selection of scaling
in parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Parameters TR150 and TR170