SSC-PRC008-EN
19
General Data TTK 60 Hz
General Data
UNIT MODELS TTK512P1 TTK518P1 TTK524P1 TTK530P1
POWER CONNECTION V/ph/Hz 200-240/1/60 200-240/1/60 200-240/1/60 200-240/1/60
MCA
1, 3
A 7.16 11.94 14.75 20.0
SYSTEM DATA
Refrigerant Type R-22 R-22 R-22 R-22
No. Refrigerant Circuits 1 1 1 1
Refrigerant Connection Type Flare Flare Flare Flare
Refrigerant Charge lb (kg) 2.64 (1.20) 2.60 (1.18) 4.40 (2.00) 6.60 (3.00)
Suction Line OD in (mm) 1/2 (12.7) 1/2 (12.7) 5/8 (15.88) 5/8 (15.88)
Liquid line OD in (mm) 1/4 (6.35) 1/4 (6.53) 3/8 (9.53) 3/8 (9.53)
COMPRESSOR
Compressor Type Rotary Rotary Rotary Scroll
No. Used 1 1 1 1
V/ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60
RLA/LRA 5.2/29.0 8.6 / 50.0 10.8 / 58.0 15.0 / 73.0
COIL
Face Area sq ft (m
2
) 3.0 (0.28) 5.60 (0.52) 5.60 (0.52) 5.60 (0.52)
Tube Size OD in (mm) 3/8 (9.35) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53)
Tube Type Inn. Grv. Inn. Grv. Inn. Grv. Inn. Grv.
Rows 2 1 1 2
Fin Type Uncoated Louver Uncoated Corrugated
Fins per inch 18 18 18 18
Refrigerant Flow Control - - - -
FAN
Fan Type Propeller Propeller Propeller Propeller
No. used 1 1 1 1
Diameter in (mm) 15 (381) 18 (457.2) 18 (457.2) 18 (457.2)
No. of Blade 5 4 4 4
Pitch Angle degree 25 30 30 30
Drive Type Direct Direct Direct Direct
Nominal Airflow
2
cfm (cmh) 800 (1359) 1600 (2717) 1600 (2717) 1600 (2717)
MOTOR
Motor Type Permanent Split Capacitor
No. of Motor 1 1 1 1
Motor hp hp (kW) 1/15 (0.04) 1/6 (0.104) 1/6 (0.104) 1/6 (0.104)
No. of Speed 1 1 1 1
Motor Speed rpm 850 900 900 900
V/ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60
RLA/LRA 0.66/0.80 1.25 / 1.53 1.25 / 1.53 1.25 / 1.53
DIMENSION (HxWxD)
4
Crated (Shipping) in 22.4 x 29.9 x 15.4 29.8 x 36.9 x 15.8
(mm) (570 x 760 x 390) (755 x 938 x 401)
Uncrated (Net) in 20.9 x 27.6 x 9.8 27.3 x 32.7 x 13.0
(mm) (530 x 700 x 250) (692 x 830 x 330)
WEIGHT
Crated (Shipping) lb (kg) 83.6 (38) 107.0 (48.5) 127.3 (47.8) 144.5 (65.7)
Uncrated (Net) lb (kg) 79.2 (36) 95.9 (43.5) 116.3 (42.8) 133.5 (60.7)
1
MCA - Minimum Circuit Ampacity ; calculated as follow : 125 % of compressor R.L.Amps plus the condenser fan motor R.L.Amps.
2
CFM is rated with standard air-dry coil.
3
At ARI system rating conditions 80
O
F-DB/67
O
F-WB indoor & 95
O
F-DB outdoor
4
For uncrated, outdoor unit’s width and depth do not include the size of the mounting feet.