SSC-PRC008-EN
21
System Performance Data
Cooling English Units
TTK512LB5 WITH MCX512GB5
AT 400 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 12.0 9.0 9.7 10.5 11.2 11.6 0.82
85
65 13.0 7.4 8.2 8.9 9.7 10.5 0.86
67 13.5 6.6 7.4 8.1 8.9 9.7 0.87
71 14.5 4.9 5.7 6.5 7.3 8.0 0.91
61 11.7 8.8 9.6 10.3 11.0 11.6 0.89
95
65 12.6 7.3 8.0 8.8 9.5 10.3 0.93
67 13.1 6.4 7.2 8.0 8.7 9.5 0.95
71 14.1 4.8 5.6 6.3 7.1 7.9 0.99
61 11.2 8.5 9.3 10.0 10.6 11.2 0.98
105
65 12.1 7.0 7.7 8.5 9.2 10.0 1.01
67 12.6 6.2 6.9 7.7 8.4 9.2 1.03
71 13.5 5.3 5.3 6.0 6.8 7.6 1.07
61 10.8 8.3 9.0 9.7 10.3 10.8* 1.06
115
65 11.6 6.7 7.5 8.2 9.0 9.7 1.10
67 12.1 5.9 6.7 7.4 8.2 8.9 1.12
71 13.0 4.3 5.0 5.8 6.6 7.3 1.16
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 13.1 MBH
AIRFLOW: 400 CFM
SYSTEM POWER: 1119 WATTS
NOM. SYSTEM AMPS: 5.3 AMPS
All temperature in Degree F