22
SSC-PRC008-EN
System Performance Data
Cooling English Units
TTK518LB5 WITH MCX518GB5
AT 475 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 17.4 13.3 14.5 15.6 16.6 17.3 1.22
85 65 18.8 11.0 12.2 13.3 14.4 15.5 1.27
67 19.5 9.8 10.9 12.1 13.2 14.3 1.29
71 20.9 7.3 8.5 9.6 10.8 11.9 1.34
61 16.9 13.1 14.2 15.4 16.3 17.3* 1.32
95 65 18.2 10.8 11.9 13.1 14.2 15.3 1.37
67 18.9 9.6 10.7 11.8 13.0 14.1 1.40
71 20.3 7.1 8.2 9.4 10.5 11.7 1.45
61 16.2 12.6 13.7 14.8 15.7 16.6* 1.44
105 65 17.5 10.4 11.5 12.6 13.7 14.8 1.49
67 18.2 9.2 10.3 11.4 12.5 13.6 1.52
71 19.5 7.8 7.9 9.0 10.1 11.2 1.58
61 15.5 12.3 13.4 14.4 15.3 16.1* 1.56
115 65 16.7 10.0 11.1 12.2 13.3 14.4 1.62
67 17.4 8.8 9.9 11.0 12.2 13.3 1.64
71 18.7 6.4 7.5 8.6 9.7 10.8 1.70
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 18.9 MBH
AIRFLOW: 475 CFM
SYSTEM POWER: 1599 WATTS
NOM. SYSTEM AMPS: 8.5 AMPS
All temperature in Degree F