System Performance Data
Cooling English Units
TTK524LB5 WITH MCX524GB5
AT 600 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 24.0 16.8 18.3 19.6 21.0 21.8 1.77
85
65 25.9 13.9 15.4 16.8 18.2 19.6 1.84
67 26.9 12.4 13.8 15.3 16.7 18.1 1.88
71 28.9 9.2 10.7 12.1 13.6 15.0 1.96
61 23.3 16.6 17.9 19.4 20.6 21.8 1.92
95
65 25.2 13.6 15.0 16.5 17.9 19.3 2.00
67 26.1 12.1 13.5 15.0 16.4 17.8 2.04
71 28.1 9.0 10.4 11.9 13.3 14.8 2.12
61 22.4 15.9 17.4 18.7 19.9 21.0 2.10
105
65 24.2 13.1 14.5 15.9 17.3 18.7 2.17
67 25.1 11.6 12.9 14.4 15.8 17.2 2.22
71 26.9 9.9 9.9 11.3 12.8 14.2 2.30
61 21.4 15.5 16.9 18.1 19.3 20.3 2.27
115
65 23.1 12.6 14.0 15.4 16.9 18.2 2.35
67 24.0 11.1 12.5 13.9 15.3 16.7 2.39
71 25.8 8.0 9.4 10.8 12.3 13.7 2.48
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 26.1 MBH
AIRFLOW: 600 CFM
SYSTEM POWER: 2335 WATTS
NOM. SYSTEM AMPS: 10.7 AMPS
All temperature in Degree F