24
SSC-PRC008-EN
System Performance Data
Cooling English Units
TTK530KB5 WITH MCX530GB5
AT 750 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 27.9 20.0 21.8 23.4 25.0 26.0 1.96
85
65 30.1 16.6 18.3 20.0 21.7 23.3 2.04
67 31.2 14.7 16.5 18.2 19.8 21.6 2.08
71 33.6 11.0 12.8 14.4 16.2 17.9 2.17
61 27.1 19.7 21.4 23.1 24.5 25.9 2.13
95
65 29.2 16.2 17.9 19.6 21.3 23.0 2.21
67 30.3 14.4 16.1 17.8 19.5 21.2 2.26
71 32.6 10.7 12.4 14.1 15.8 17.6 2.35
61 26.0 19.0 20.7 22.3 23.6 25.0 2.32
105
65 28.1 15.6 17.2 19.0 20.6 22.3 2.41
67 29.2 13.8 15.4 17.1 18.8 20.5 2.45
71 31.3 11.8 11.8 13.5 15.2 16.9 2.55
61 24.9 18.4 20.1 21.6 23.0 24.2 2.51
115
65 26.8 15.0 16.7 18.4 20.1 21.7 2.61
67 27.9 13.2 14.9 16.5 18.3 19.9 2.65
71 30.0 9.6 11.2 12.9 14.6 16.3 2.75
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 30.3 MBH
AIRFLOW: 750 CFM
SYSTEM POWER: 2634 WATTS
NOM. SYSTEM AMPS: 17.2 AMPS
All temperature in Degree F