30
SSC-PRC008-EN
System Performance Data
Cooling English Units
TTK524PB WITH MCX524GB
AT 600 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 22.3 15.2 16.5 17.8 19.0 19.7 2.14
85 65 24.1 12.6 13.9 15.2 16.5 17.7 2.22
67 25.1 11.2 12.5 13.8 15.1 16.4 2.27
71 26.9 8.4 9.7 10.9 12.3 13.6 2.36
61 21.7 15.0 16.2 17.5 18.6 19.7 2.32
95 65 23.4 12.3 13.6 14.9 16.2 17.5 2.41
67 24.3 10.9 12.2 13.5 14.8 16.1 2.46
71 26.1 8.2 9.4 10.7 12.0 13.3 2.56
61 20.8 14.4 15.7 16.9 18.0 19.0 2.53
105 65 22.5 11.8 13.1 14.4 15.7 17.0 2.62
67 23.4 10.5 11.7 13.0 14.3 15.6 2.67
71 25.1 8.9 9.0 10.2 11.6 12.8 2.78
61 19.9 14.0 15.3 16.4 17.5 18.4 2.73
115 65 21.5 11.4 12.7 13.9 15.2 16.5 2.84
67 22.4 10.0 11.4 12.6 13.9 15.1 2.89
71 24.0 7.3 8.5 9.8 11.1 12.4 2.99
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95 oF
GROSS CAPACITY: 24.3 MBH
AIRFLOW: 600 CFM
SYSTEM POWER: 2739 WATTS
NOM. SYSTEM AMPS: 12.8 AMPS
All temperature in Degree F