40
SSC-PRC008-EN
System Performance Data
Cooling English Units
TTK530P1 WITH MCX530G1
AT 750 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 28.3 19.9 21.7 23.3 24.9 25.8 2.51
85 65 30.6 16.5 18.2 19.9 21.6 23.2 2.61
67 31.8 14.7 16.4 18.1 19.7 21.5 2.66
71 34.1 11.0 12.7 14.3 16.1 17.8 2.77
61 27.5 19.6 21.3 23.0 24.4 25.8 2.72
95 65 29.7 16.2 17.8 19.5 21.2 22.9 2.83
67 30.8 14.3 16.0 17.7 19.4 21.1 2.89
71 33.1 10.7 12.3 14.1 15.7 17.5 3.00
61 26.4 18.9 20.6 22.2 23.5 24.9 2.97
105 65 28.5 15.5 17.2 18.9 20.5 22.2 3.08
67 29.7 13.7 15.3 17.1 18.7 20.4 3.14
71 31.8 11.7 11.8 13.4 15.1 16.8 3.26
61 25.3 18.4 20.0 21.5 22.9 24.1 3.21
115 65 27.3 14.9 16.6 18.3 20.0 21.6 3.34
67 28.3 13.1 14.9 16.5 18.2 19.8 3.39
71 30.5 9.5 11.2 12.8 14.6 16.2 3.51
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
AIRFLOW: 600 CFM
GROSS CAPACITY: 30.8 MBH
AIRFLOW: 750 CFM
SYSTEM POWER: 3324 WATTS
NOM. SYSTEM AMPS: 15.3 AMPS
All temperature in Degree F