Principles of Operation of
the Module UCM-CLD
7RLC-SVU02F-E4
Parameters and setpoints within each menu
Menu Parameters/setpoints Range
Minimum/Maximum
Chiller Report Menu Active Chilled Water Setpoint
Evaporator Entering/ Leaving Chilled Water Temperature
Condenser Entering / Leaving Chilled Water Temperature
Active Ice-Storing Setpoint
Active Hot Water Setpoint
Entering/Leaving Hot Water Temperature
Current Active Setpoint limits -17.8°/18.3°C
Evaporator/Condenser Waterflow
Ambient Air Temperature
Sources of setpoints (Tracer, local CLD, external)
Custom Report Menu Custom-built by the operator (Can contain up to 20 settings)
Refrigerant Report Menu Condenser/Evaporator Refrigerant Pressures
Refrigerant Temperature in Condenser
Refrigerant Temperature in Evaporator
Compressor Report Menu Compressor Status
Time and Start Counters
Amps (% RLA)
Oil Temperature (GP compressor only)
Operator Settings Menu Setpoint Source
External Chilled Water Setpoint
External Hot Water Setpoint
Chilled Water Pump Operation
Chilled Water Pump Off Delay 1 min/30 min
Ice Machine Control*
Panel Ice Termination Setpoint -6.6°/-0.5°C
Low Ambient Lockout
Low Ambient Lockout Setpoint -28.8°/15.5°C
Front Panel Current Limit Setpoint 40%/120%
Front Panel Hot Water Setpoint 25°/60°C
Front Panel Chilled Water Setpoint -17.8°/18.3°C
Design Delta Temperature Setpoint 2.2°/16.6°C
External Current Limit Setpoint
Differential to Start Setpoint 1.1°/16.6°C
Chilled Water Reset Type
Type Reset Ratio
Type Start Reset Setpoint
Type Max Reset Setpoint 0.0°/11.1°C