EasyManua.ls Logo

Trane VariTrac - Install Communicating Bypass Damper Assembly

Trane VariTrac
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VariTrac Installation
Question: Can both 24Vac power and sensor wiring share the same conduit? ____.
Why or why not? _____________________________________________________
Install Communicating Bypass Damper Assembly
Reference: VariTrac Installation Manual (VAV-SVN03A-EN), Pages 21 through 22
Note:
The communicating sensor/bypass assembly is normally located between the
supply fan and the bypass damper in the least turbulent location possible. It is
recommended that the d stance between the con roller assembly and the nearest
upstream transition be at least 2 to 3 equivalent duct diameters.
i t
6. Locate the communicating sensor/bypass assembly housing near the VariTac lab equipment
and remove metal cover.
7. Verify address DIP switches on the communicating sensor/bypass UCM board are set to
address ‘ 33 ’.
Note: The communicating sensor assembly UCM address DIP switches are set at the
factory to Address 33.
8. Connect the communications link wiring to terminalsTB2-1 and TB2-2, TB2-3 and TB-2-4
using the pre-configured wiring harness provided. Observe (+) and (-) polarity on the link.
Note: A pre-configured wiring harness is provided to connect both 24Vac and the
communications link to the communicating bypass/damper UCM.
9. Connect 24Vac power to terminals TB1-1 (24V) and TB-2 (ground) on the UCM
Caution: It is not recommended that 24Vac power be shared between controllers.
However, if controllers share a common transformer, polarity must be observed on 24Vac
connections on UCMs that share the same transformer.
03- VariTrac Installation Workshop.doc 3-4

Related product manuals