IPB-99-7-EN-10-6-99 11
Performance
Data Cooling Metric Units
WCC030FD00B AT 1698 CMH (GROSS CAPACITY IN KILOWATTS)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.6 6.9 7.4 8.0 8.5 8.8* 2.3
29.4 17.2 9.2 5.9 6.4 6.9 7.5 8.0 2.4
19.4 9.9 4.7 5.3 5.8 6.3 6.9 2.4
21.7 10.6 3.6 4.1 4.7 5.2 5.7 2.5
15.0 8.4 6.8 7.4 7.9 8.4* 8.6* 2.4
32.2 17.2 9.0 5.8 6.3 6.9 7.4 7.9 2.5
19.4 9.7 4.7 5.2 5.7 6.2 6.8 2.6
21.7 10.3 3.5 4.0 4.5 5.1 5.6 2.6
15.0 8.2 6.7 7.3 7.8 8.3* 8.4* 2.5
35.0 17.2 8.8 5.7 6.2 6.8 7.3 7.8 2.6
19.4 9.4 4.6 5.1 5.6 6.2 6.7 2.7
21.7 10.1 3.4 3.9 4.5 5.0 5.5 2.8
15.0 7.9 6.6 7.1 7.7 8.1* 8.2* 2.7
37.8 17.2 8.5 5.6 6.1 6.7 7.2 7.7 2.7
19.4 9.1 4.5 5.0 5.5 6.0 6.6 2.8
21.7 9.8 3.3 3.8 4.3 4.9 5.4 2.9
15.0 7.7 6.5 7.1 7.6 7.8* 8.0* 2.8
40.6 17.2 8.2 5.5 6.0 6.5 7.1 7.6 2.8
19.4 8.8 4.3 4.9 5.4 5.9 6.4 2.9
21.7 9.4 3.2 3.7 4.2 4.7 5.3 3.0
15.0 7.1 6.3 6.8 7.2* 7.4* 7.6* 3.0
46.1 17.2 7.7 5.2 5.8 6.3 6.8 7.4 3.1
19.4 8.2 4.1 4.6 5.2 5.7 6.2 3.1
21.7 8.8 2.9 3.5 4.0 4.5 5.0 3.2
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1486 1910
TOTAL CAP. X0.98 X1.02
SENS. CAP. X0.94 X1.05
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9435 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2673 WATTS
I.D. FAN POWER = 340 WATTS
O.D. FAN POWER = 250 WATTS
E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCT. AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
WCC040FD00B AT 2250 CMH (GROSS CAPACITY IN KILOWATTS)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 10.9 9.1 9.8 10.5 11.0* 11.3* 2.6
29.4 17.2 11.7 7.6 8.4 9.1 9.8 10.6 2.7
19.4 12.6 6.0 6.8 7.5 8.2 9.0 2.8
21.7 13.5 4.4 5.2 5.9 6.6 7.4 2.8
15.0 10.7 9.0 9.7 10.5 10.9* 11.2* 2.7
32.2 17.2 11.5 7.5 8.3 9.0 9.8 10.5 2.8
19.4 12.4 5.9 6.7 7.4 8.2 8.9 2.9
21.7 13.2 4.3 5.1 5.8 6.6 7.3 3.0
15.0 10.5 8.9 9.6 10.4 10.8* 11.0* 2.9
35.0 17.2 11.3 7.4 8.2 8.9 9.7 10.4 3.0
19.4 12.2 5.9 6.6 7.4 8.1 8.8 3.0
21.7 13.0 4.2 5.0 5.7 6.5 7.2 3.1
15.0 10.2 8.8 9.5 10.3* 10.5* 10.8* 3.0
37.8 17.2 11.0 7.3 8.1 8.8 9.6 10.3 3.1
19.4 11.8 5.7 6.5 7.2 8.0 8.7 3.2
21.7 12.7 4.1 4.9 5.6 6.4 7.1 3.2
15.0 9.9 8.6 9.4 10.0* 10.3* 10.5* 3.2
40.6 17.2 10.7 7.2 7.9 8.7 9.4 10.2 3.2
19.4 11.5 5.6 6.4 7.1 7.9 8.6 3.3
21.7 12.3 4.0 4.7 5.5 6.2 7.0 3.4
15.0 9.4 8.4 9.2 9.6* 9.8* 10.0* 3.5
46.1 17.2 10.1 7.0 7.7 8.4 9.2 9.9 3.5
19.4 10.8 5.4 6.1 6.9 7.6 8.4 3.6
21.7 11.6 3.8 4.5 5.2 6.0 6.7 3.6
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1953 2547
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.94 X1.06
COMPR. KW X0.98 X1.02
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY =12189 KW
AIRFLOW = 2250 CMH
COMPRESSOR POWER = 3022 WATTS
I.D. FAN POWER = 560 WATTS
O.D. FAN POWER = 500 WATTS
E.E.R. = 9.70 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCT. AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
WCC050FD00B AT 2845 CMH (GROSS CAPACITY IN KILOWATTS)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 14.0 11.8 12.8 13.7 14.3* 14.6* 4.2
29.4 17.2 15.0 10.0 10.9 11.9 12.8 13.8 4.3
19.4 16.1 7.9 8.9 9.8 10.8 11.7 4.5
21.7 17.2 5.8 6.8 7.7 8.7 9.6 4.6
15.0 13.9 11.8 12.7 13.7 14.2* 14.5* 4.2
32.2 17.2 14.9 9.9 10.9 11.8 12.7 13.7 4.3
19.4 16.0 7.9 8.8 9.8 10.7 11.7 4.4
21.7 17.1 5.8 6.7 7.7 8.6 9.6 4.5
15.0 13.7 11.7 12.7 13.6 14.0* 14.4* 4.1
35.0 17.2 14.7 9.8 10.8 11.7 12.7 13.7 4.2
19.4 15.8 7.8 8.8 9.7 10.6 11.6 4.3
21.7 16.9 5.7 6.7 7.6 8.6 9.5 4.5
15.0 13.2 11.5 12.4 13.3* 13.6* 13.9* 4.3
37.8 17.2 14.2 9.6 10.6 11.5 12.5 13.4 4.4
19.4 15.2 7.6 8.5 9.5 10.4 11.4 4.5
21.7 16.3 5.5 6.4 7.4 8.4 9.3 4.6
15.0 12.7 11.3 12.2 12.9* 13.2* 13.5* 4.5
40.6 17.2 13.7 9.4 10.3 11.3 12.2 13.2 4.6
19.4 14.6 7.4 8.3 9.3 10.2 11.2 4.7
21.7 15.7 5.3 6.2 7.2 8.1 9.1 4.8
15.0 11.7 10.8 11.7* 12.0* 12.3* 12.6* 4.8
46.1 17.2 12.6 9.0 9.9 10.9 11.8 12.6* 4.9
19.4 13.5 6.9 7.9 8.8 9.8 10.7 5.0
21.7 14.4 4.9 5.8 6.7 7.7 8.6 5.1
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 2462 3227
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.94 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY =15822 KW
AIRFLOW = 2845 CMH
COMPRESSOR POWER = 4339 WATTS
I.D. FAN POWER = 680 WATTS
O.D. FAN POWER = 500 WATTS
E.E.R. = 9.35 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCT. AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES C.