SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Wireless Comm
January 2014 BAS-SVX40B-EN
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
WCI
Installation, Operation,
and Maintenance

Questions and Answers

  • O
    odayAug 12, 2025
    What to do if Trane Recording Equipment has no communication?
    • A
      Austin MichaelAug 12, 2025
      If your Trane Recording Equipment experiences a loss of communication due to power loss, the coordinator WCI will re-initiate the network as soon as power is restored. Similarly, if a signal obstruction is the cause, the coordinator WCI will re-initiate the network once communication is re-established. You can also try moving network components closer to extend the radio range or cycle power on the controller or Tracer SC connected to the WCI.
  • P
    pgomezAug 19, 2025
    How to fix Trane X13790901010 Recording Equipment WCI that does not join network?
    • C
      Cameron ArnoldAug 19, 2025
      If your WCI does not join the network, allow it more time to connect. If the network closes prematurely, reopen it using the OPEN NET button on another WCI. For factory-addressed WCIs, ensure the address is correct and verify each WCI address post-installation. Check the sensor for error codes, if installed. Initiate network formation and resolve any exceptions. Also, check that the WCI and the corresponding controller are wired correctly and powered on. Trying a different channel by selecting a different net address may also help. Relocating the WCI or adding a repeater can improve connectivity. If all else fails, consider replacing the WCI.
  • A
    alvinpierceAug 27, 2025
    What to do if Trane X13790901010 Tracer SC does not communicate with WCI?
    • M
      Mr. Timothy FrederickAug 27, 2025
      If your Tracer SC is not communicating with the WCI, verify that the WCI is properly wired to the Tracer SC. Also, ensure that the wireless link on the Tracer SC is enabled, configured to match the WCI address, and is unique within the building. Moving network components within radio range, breaking up networks to make them smaller, or adding a repeater can also help.
  • D
    Diana JonesSep 3, 2025
    What to do if Trane X13790901010 sensor does not communicate with WCI?
    • G
      Gwendolyn PowersSep 3, 2025
      If a sensor is not communicating with the WCI, make sure the sensor address matches the unit controller address, focusing on matching addresses rather than arrow directions. You can press the test button on the sensor to force association. If that doesn't work, use Tracer TU to update WCI to the latest firmware. If problems persist, consider replacing the defective device.