EasyManua.ls Logo

Trane X13790901010 - Page 15

Trane X13790901010
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX40B-EN 15
Mounting and Wiring the WCI
Figure 6. Wiring the WCI to a Tracer SC
Figure 7. Wiring multiple WCIs to a Tracer SC
Tracer SC
PM014
WCI wiring
LINK +
LINK –
+ 24VDC
IMC IMC+
Grou nd 2 4 Vd c
Gray = LINK -
Blue = LINK +
Black = Ground
Red = 24 Vdc
Connect both 2-connector
screw terminal blocks to
either of the IMC terminals
on the PM014.
WCI WCIWCIWCI
WCI WCIWCIWCI
Tracer SC
PM014
Notes:
A maximum of eight WCIs can be
daisy-chained to the Tracer SC.
Use both IMC terminals on the
PM014 for wiring multiple WCIs
(see the detail in Figure 6).
The WCIs on both links can span a
total of 200 meters.