4 22-1800-15
Product Specifications
Model No. 1 4TWX5018B1 4TWX5024B1 4TWX5030B1 4TWX5036B1
Electrical Data V/Ph/Hz 2 208/230/1/60 200/230/1/60 208/230/1/60 208/230/1/60
Min Cir Ampacity 9 11 15 18
Max Fuse Size (Amps) 15 15 25 30
Compressor CLIMATUFF
®
CLIMATUFF
®
CLIMATUFF
®
CLIMATUFF
®
RL Amps - LR Amps 6.4 - 38.6 8.3 - 58 11.3 - 68.2 13.2-63
Outdoor Fan FL Amps 0.70 0.74 .92 1.0
Fan HP 1/8 1/8 1/5 1/5
Fan Dia (inches) 23 23 27.5 27.5
Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™
Refrigerant R-410A 5/14-LB/OZ 7/02-LB/OZ 8/02-LB/OZ 7/13-LB/OZ
Line Size - (in.) O.D. Gas 3 5/8 5/8 3/4 3/4
Line Size - (in.) O.D. Liquid 3 3/8 3/8 3/8 3/8
Dimensions H x W x D (Crated) 39.1 x 30 x 33 43.6 x 30.1 x 33 45.4 x 35.1 x 38.7 44.9 x 35 x 37.9
Weight - Shipping 225 242 283 293
Weight - Net 190 208 239 247
Start Components YES YES YES YES
Sound Enclosure YES YES YES YES
Compressor Sump Heat YES YES YES YES
Optional Accessories: 4
Anti-short Cycle Timer TAYASCT501A TAYASCT501A TAYASCT501A TAYASCT501A
Evaporator Defrost Control A/C AY28X084 AY28X084 AY28X084 AY28X084
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 BAYISLT101
Snow Leg - Base & Cap 4" High BAYLEGS002 BAYLEGS002 BAYLEGS002 BAYLEGS002
Snow Leg - 4" Extension BAYLEGS003 BAYLEGS003 BAYLEGS003 BAYLEGS003
Hard Start Kit Scroll
Extreme Condition Mounting Kit BAYECMT004 BAYECMT004 BAYECMT004 BAYECMT004
Refrigerant Lineset 5 TAYREFLN950 TAYREFLN950 TAYREFLN7* TAYREFLN7*
1 Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on AHRI Standard 210/240.
2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
3 Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line.
For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0
. (
denotes latest revision)
4 For accessory description and usage, see page 5.
5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.
General
Data
63 125 250 500 1000 2000 4000 8000
4TWX5018B 72 49.9 55.8 62.8 66.1 65.8 64.7 58.5 53.5
4TWX5024B 72 47.4 54.1 60.2 62.9 67.4 63.6 57.6 49.9
4TWX5030B 72 49.8 57.1 61 65.8 66.3 63.8 60.3 53.5
4TWX5036B 72 47.5 55.4 58.8 65 65.5 61.9 58.6 47.8
4TWX5042B 73 55.1 51.7 59.7 64.9 66.8 62.9 60.4 45.9
4TWX5049E 72 43.7 51.2 54.5 61 61.5 57.1 51.3 40.7
4TWX5061E 74 33.1 56.2 60.1 64.4 66 59.5 54.2 43.5
Note: Rated in accordance with AHRI Standard 270-2008.
SOUND POWER
LEVEL [dB(A)]
A-weighted Sound Power Level [dB(A)]
MODEL