Product Specifications
57
Table 4 : Product Data
Model Fuel Input BTU/hr AFUE % DOE Heating Net IBR Shipping
Capacity BTU/Hr. Rating BTU/Hr. Weight
Capacity Gals.
Note 1 Note 2 Note 3 Note 4 Lbs.
PG-150 Natural & Propane 150,000 84 126,000 107,500 345
PG-199 Natural & Propane 199,000 84 167,500 142,500 345
PG PLUS-150 (Note 5) Natural & Propane 150,000 85 127,500 108,500 345
PG PLUS-199 (Note 5) Natural & Propane 199,000 86 171,500 145,500 345
Domestic Primary 10 Min. Continuous
Model Capacity Capacity Peak Flow 1st Hour Flow @ 70ºF
Gals. Gals. Gals. Rating gph Rise gph
PG-150 & PG PLUS-150 20 22 70 230 190
PG-199 & PG PLUS-199 17 20 80 290 250
Note 1: Input ratings are shown for sea level applications. The appliance automatically derates the input at
approximately 2% for every 1,000 feet of altitude. No alterations to the appliance is required.
Note 2: Based on the given AFUE the MODULATING DELTA PG PLUS Models meet the energy efficiency
guidelines established by Energy Star.
Note 3: The heating capacity is based on the test requirements of the U.S. Department of Energy.
Note 4: The IBR rating is based on a piping and pick up allowance of 1.15. This allowance should be sufficient
for the standard radiation requirements for a building load.
Note 5: The PG PLUS Models must not vent as a Category I (Chimney Vent) appliance.