Prestige Solo Features
• Light weight construction for wall mounting
• Approved for zero clearance to combustibles
• 3” or 4” PVC, CPVC, PP, or AL29-4C venting up to 100
equivalent feet
• Limited 10 year warranty on heat exchanger
Approvals
• 96% AFUE Efficiency
• ENERGY STAR Qualified
• ANSI Z21.13 and CSA 4.9 Boiler Standards Compliance
• ASME Boiler Certification – ASME “H” Stamp
• Low NOx operation exceeding SCQMD 2012 regulations
Stainless Steel Fire Tube Heat Exchanger
• 439 Stainless Steel heat exchanger construction
• Low pressure drop minimizes circulator size
• High water content provides stable temperature control
• Self cleaning flue ways reduce maintenance
• Suitable for use with propylene glycol up to 50% concen-
tration.
TriMax Control System
• Graphical display with 6 navigation buttons
• EZ Setup allows quick and easy boiler settings adjustment
• Logging function records sensor readings for system opti-
mization and troubleshooting
• Lockout screen includes a text description with basic
troubleshooting information
• Outdoor temperature reset to maximize efficiency
• Two space heating call inputs with independent outdoor
reset curves
• Domestic hot water priority with optional time-out
• Integrated cascade control for up to 6 Prestige boilers
• 0-10 VDC Modulation input
• Modbus building management system (BMS) interface
• Warm weather shutdown option
• Optional boiler freeze protection
• Capability to control up to 4 circulators
- Central heating (CH) circulator
- Domestic hot water (DHW) circulator
- Auxiliary boiler circulator
- System circulator
Standard Equipment
• Stainless steel premix burner
• Direct spark ignition with variable speed blower
• Full modulation from 25% to rated input
• Automatic air vent
• ASME 30 PSI pressure relief valve
• Integrated pressure and temperature gauge
• Outdoor temperature sensor
• Automatic low water cutoff feature
• High temperature limit safety control
• Line voltage terminal strip with individual fuses
• Low voltage terminal strip with removable jumpers for
manual or automatic reset limits
• Swing down control panel for easy access and servicing
• Alarm contact
• Polypropylene condensate pan and internal flue pipe
• Polypropylene vent/air connections with test ports
prestige
Fully Condensing
Water Boiler
Engineering Submittal
Prestige Solo 175
Project / Location:
Consulting Engineer / Architect:
Mechanical Contractor:
Date:
1
2012-22 Prestige Solo 175 SubmittalDate 2/15/12
-
E
N
V
I
R
O
N
M
E
N
T
A
L
L
Y
F
R
I
E
N
D
L
Y
-
L
O
W
N
O
X
-
E
X
C
E
E
D
S
2
0
1
2
S
C
A
Q
M
R
E
Q
U
I
R
E
M
E
N
T
S