5.1.8. Run-on time
A time starting from the last detected movement in the room; when the run-on time expires, the fade time begins.
If further movement is detected during the run-on time, it starts over again.
You can choose whether you want the basicDIM DGC module to switch off the light completely or to dim it down to the second light
level after the run-on time.
The run-on time may vary depending on the profile used. It can be changed using the basicDIM DGC Programmer or the
masterCONFIGURATOR software (see "Reference list" at the end of this document).
Response to commands via DALI IN:
For a DAP command > 0, Recall Max, Recall Min the Run-on time is started.
Response to neighbourhood function:
If as response to the neighbourhood function the presence value was set the run-on time is started
Response to scene commands:
Responses to scene commands are described at .Scenes, p. 22
5.1.9. Switch-off delay
Time for which the absence value is maintained if no movement is detected.
The switch-off delay and the absence level differ depending on the profile used; these parameters may be changed using the
basicDIM DGC Programmer or the masterCONFIGURATOR software (see "Reference list" at the end of this document).
Response to neighbourhood function:
If as response to the neighbourhood function the absence value was set the switch-off delay time is started
5.1.10. Absence level
Level to which the luminaire group switches during the switch-off delay.