Increasing or decreasing the nozzle size or supply water pressure can vary the output capacity of this humidier. It
is recommended that the humidier NOT be used with water pressures below 40 PSI, otherwise, the mist may be
adversely affected.
This humidier comes standard with a .75 GPH (oil) nozzle with a hollow spray pattern. Alternatively sized nozzles
may be purchased from your local HVAC supply house or plumbing supply outlet. If the water pressure uctuates or is
excessive, a pressure regulator should be installed in the water line supplying the humidier.
The following chart illustrates the capacity of different nozzles at varying water pressures. The capacity listed on the
nozzle is for #2 fuel oil at 100 psi and should not be considered relative to the water capacity of this humidier.
Nozzle
Pressure
(PSI)
Nozzle Size
0.4 0.5 0.75 1
GPH GPD GPH GPD GPH GPD GPH GPD
40 0.23 5.5 0.28 6.8 0.43 10.2 0.57 13.7
45 0.24 5.8 0.30 7.2 0.45 10.9 0.60 14.5
50 0.25 6.1 0.32 7.6 0.48 11.5 0.64 15.3
55 0.27 6.4 0.33 8.0 0.50 12.0 0.67 16.0
60 0.28 6.7 0.35 8.4 0.52 12.5 0.70 16.7
65 0.29 7.0 0.36 8.7 0.54 13.1 0.73 17.4
70 0.30 7.2 0.38 9.0 0.56 13.6 0.75 18.1
75 0.31 7.5 0.39 9.4 0.58 14.0 0.78 18.7
80 0.32 7.7 0.40 9.7 0.60 14.5 0.80 19.3
85 0.33 8.0 0.41 10.0 0.62 14.9 0.83 19.9
90 0.34 8.2 0.43 10.2 0.64 15.4 0.85 20.5
95 0.35 8.4 0.44 10.5 0.66 15.8 0.88 21.1
100 0.36 8.6 0.45 10.8 0.68 16.2 0.90 21.6
Output Capacity
NOTE:
Due to the operation cycle of the furnace and humidier, it may take from 2-5 days to reach the proper
humidication level.