9
Wiring Power Input
NGI-U08C2 with 6-Pin Terminal Block
Use “PWR” for Primary Power input and “RPS” for Redundant Power
input.ThetopviewofTerminalBlockisshowninthegurebelow:
Caution:
• Use copper conductors only.
• Use wiring cable with rated temperature at least 221°F
(105°C).
•Tightenthewiretoatorquevalue4.5lb•in(0.5N•m).
• The wire gauge for the terminal block should range between
12~24 AWG (4~0.25 mm2).
To insert the power wire and connect the 24~48VDC at a maximum of
0.4A DC power to the power terminal block:
• Useaatheadscrewdrivertoloosenthewireclampscrews.
Insert the negative/positive DC wires into the PWR-/PWR+ terminals,
respectively.
• Tighten the wire-clamp screws to prevent the wires from loosening.
ATTENTION: Use a power supply rated for 24~48VDC.
The device power must be supplied by SELV circuit.
Terminal Block