TRISAN S8 Technical specifications
Portable RCD Class I
Differential Leakage current for less than 1mA……………………………………………..PASS
Polarity A –N swap detect
Neutral open detect
Active open detect
Earth open detect
Electrical continuity > 10k ohm
Short circuit A –N < 10k ohm
Earth continuity <1 Ohm @ 200mA
Trip time measurement < 40ms. @ 10mA For 0° and 180° ……………………………… PASS
Trip time measurement <300ms. @ 30mA For 0° and 180° ……………………………… PASS
Measurements made between LEADS socket inlet and RUN socket outlet
Fixed RCD
Electrical continuity:
Polarity A –N swap detect
Neutral open detect
Active open detect
Earth open detect
Supply Earth continuity check before test
Trip time measurement < 40ms. @ 10mA For 0° and 180° ……………………………… PASS
Trip time measurement <300ms. @ 30mA For 0° and 180° ……………………………… PASS
Measurements made on mains supply inlet to tester.
Note: Building mains supply will be interrupted for duration of test.
Ensure batteries are installed in the tester for RCD tests to function properly.