Nopower GFCIand/orbreakertripped
Powersupplyfusehasblown
Transientvoltagesurgesuppressor
damaged
Powersupplydamaged
ResetGFCIand/orbreaker
Replacepowersupplyfuse-seeFuse
Replacementsection
Replacetransientvoltagesurge
suppressor(TVSS)
ReplacepowersupplyanduseaTVSS
GFCIorbreaker
repeatedlytrips
Connectionbetweenlampandlampcord
iswet
Short-circuitintheelectricalassembly
Cleananddrythecordandendlamp
pins,checkunitforleaksorcondensation
Replacepowersupply
Leakatinletor
outlet
Threadedpipefittingsareleaking Cleanthreads,resealwithTeflontape
andretighten
Leakdetectedfrom
areaofchamber
Condensationofmoistaironcold
chamber(slowaccumulation)
O-ringdamaged,deterioratedor
incorrectlyinstalled
Sleeveboltnottightenough
Controlhumidityorrelocateunit
Inspectandreplaceifdeteriorated
Ensurenutisturnedcompletely(tostops)
Alarm
SeeControl Panelsection SeeControl Panelsection
Systemisoperating
butwatertests
revealbacterial
contamination
EquipmentdownstreamofUVsystem
isactingasabreedinggroundfor
pathogens
Pathogensareresidinginthedistribution
linespost-UV
Recontaminationfrompipedead-ends
EnsureUVisthelastpieceoftreatment
equipment
Ensurealldistributionlineshave
beendisinfectedwithchlorine-see
Disinfecting the Water Linessection
Removeanypipedead-endsandflush
withchlorine-seeDisinfecting the
Water Linessection
Possible cause Possible solutionSymptom